dc.description.abstractFlow boiling was experimentally studied using coolant HFE-7000 for two types of parallel microchannels: a plain-wall microchannel and a microchannel with structured reentrant cavities on the side walls. Flow morphologies, boiling inceptions, heat transfer coefficients, and critical heat fluxes were obtained and studied for mass fluxes ranging from G=164 kg/m2 s to G=3025 kg/m2 s and mass qualities (energy definition) ranging from x=−0.25 to x=1. Comparisons of the performance of the enhanced and plain-wall microchannels were carried out. It was found that reentrant cavities were effective in reducing the superheat at the onset of nucleate boiling and increasing the heat transfer coefficient. However, they did not seem to increase the critical heat flux.
dc.publisherThe American Society of Mechanical Engineers (ASME)
dc.titleFlow Boiling of Coolant (HFE-7000) Inside Structured and Plain Wall Microchannels
dc.typeJournal Paper
dc.journal.volume131
dc.journal.issue12
dc.journal.titleJournal of Heat Transfer
dc.identifier.doi10.1115/1.3220674
dc.journal.fristpage121011
dc.identifier.eissn1528-8943
dc.keywordsFlow (Dynamics)
dc.keywordsCoolants
dc.keywordsBoiling
dc.keywordsMicrochannels
dc.keywordsHeat transfer coefficients
dc.keywordsCritical heat flux
dc.keywordsCavities
dc.keywordsFlux (Metallurgy) AND Channels (Hydraulic engineering)
dc.treeJournal of Heat Transfer:;2009:;volume( 131 ):;issue: 012