Show simple item record

dc.contributor.authorFarhad Behafarid
dc.contributor.authorMehdi N. Bahadori
dc.date.accessioned2017-05-09T00:23:31Z
dc.date.available2017-05-09T00:23:31Z
dc.date.copyrightJune, 2007
dc.date.issued2007
dc.identifier.issn0195-0738
dc.identifier.otherJERTD2-26544#117_1.pdf
dc.identifier.urihttp://yetl.yabesh.ir/yetl/handle/yetl/135628
dc.description.abstractThe power output of gas turbines (GT) reduces greatly with the increase of the inlet air temperature. This is a serious problem because gas turbines have been used traditionally to provide electricity during the peak power demands, and the peak power demands in many areas occur on summer afternoons. An aquifer thermal energy storage (ATES) was employed for cooling of the inlet air of the GT. Water from a confined aquifer was cooled in winter and was injected back into the aquifer. The stored chilled water was withdrawn in summer to cool the GT inlet air. The heated water was then injected back into the aquifer. A 20MW GT power plant with 6 and 12h of operation per day, along with a two-well aquifer, was considered for analysis. The purpose of this investigation was to estimate the GT performance improvement. The conventional inlet air cooling methods such as evaporative cooling, fogging and absorption refrigeration were studied and compared with the ATES system. It was shown that for 6h of operation per day, the power output and efficiency of the GT on the warmest day of the year could be increased from 16.5 to 19.7MW and from 31.8% to 34.2%, respectively. The performance of the ATES system was the best among the cooling methods considered on the warmest day of the year. The use of ATES is a viable option for the increase of gas turbines power output and efficiency, provided that suitable confined aquifers are available at their sites. Air cooling in ATES is not dependent on the wet-bulb temperature and therefore can be used in humid areas. This system can also be used in combined cycle power plants.
dc.publisherThe American Society of Mechanical Engineers (ASME)
dc.titlePerformance Evaluation of a Gas Turbine Operating Noncontinuously with its Inlet Air Cooled Through an Aquifer Thermal Energy Storage
dc.typeJournal Paper
dc.journal.volume129
dc.journal.issue2
dc.journal.titleJournal of Energy Resources Technology
dc.identifier.doi10.1115/1.2719203
dc.journal.fristpage117
dc.journal.lastpage124
dc.identifier.eissn1528-8994
dc.keywordsTemperature
dc.keywordsWater
dc.keywordsCooling
dc.keywordsThermal energy storage
dc.keywordsPower stations AND Gas turbines
dc.treeJournal of Energy Resources Technology:;2007:;volume( 129 ):;issue: 002
dc.contenttypeFulltext


Files in this item

Thumbnail

This item appears in the following Collection(s)

Show simple item record