    Viability of Dynamic Cooling Control in a Data Center Environment

    Thumbnail
    View/Open
    JEPAE4-26263#137_1.pdf (495.5Kb)
    Date
    2006
    Author
    Timothy D. Boucher
    David M. Auslander
    Cullen E. Bash
    Clifford C. Federspiel
    Chandrakant D. Patel
    Metadata
    Show full item record
    Abstract
    Data center thermal management challenges have been steadily increasing over the past few years due to rack level power density increases resulting from system level compaction. These challenges have been compounded by antiquated environmental control strategies designed for low power density installations and for the worst-case heat dissipation rates in the computer systems. Current data center environmental control strategies are not energy efficient when applied to the highly dynamic, high power density data centers of the future. Current techniques control the computer room air conditioning units (CRACs) based on the return air temperature of the air—typically set near 20°C. Blowers within the CRACs are normally operated at maximum flow rate throughout the operation of the data center unless they are equipped with nonstandard variable frequency drives. At this setting the blowers typically provide significantly more airflow than is required by the equipment racks to prevent recirculation and the subsequent formation of hot spots. This strategy tends to be overly conservative and inefficient. As an example air entering a given system housed in a rack undergoes a temperature rise of 15°C due to the heat added by the system. The return air control strategy strives to keep the entire room at a fixed temperature. Therefore in a typical data center the CRAC supply temperature, and hence the air entering the racks, is 13–15°C and the CRAC return is 20–22°C. At these settings the CRACs can consume almost as much energy as the computer equipment they are cooling [2002, “ Towards Planetary Scale Computing – Technical Challenges for Next Generation Internet Computing,” THERMES 2002, Santa Fe, NM; The Uptime Institute, “Heat Density Trends in Data Processing, Computer Systems and Telecommunications Equipment,” White Paper issued by The Uptime Institute, 2000.]. Experiments conducted by the authors using these CRAC settings show that nearly 0.7W is consumed by the environmental control system for every 1W of heat dissipated by the computer equipment in the authors’ experimental facility indicating that the energy efficiency of standard data center environmental control systems is poor. This study examines several opportunities for improving thermal management and energy performance of data centers with automatic control. Experimental results are presented that demonstrate how simple, modular control strategies can be implemented. Furthermore, experimental data is presented that show it is possible to improve the energy performance of a data center by up to 70% over current standards while maintaining proper thermal management conditions.
    URI
    http://yetl.yabesh.ir/yetl/handle/yetl/133543
    Collections
    • Journal of Electronic Packaging

    DSpace software copyright © 2002-2015  DuraSpace
    Contact Us | Send Feedback
    Theme by 
    @mire NV
     

     

    Browse

    All of DSpaceCommunities & CollectionsBy Issue DateAuthorsTitlesSubjectsThis CollectionBy Issue DateAuthorsTitlesSubjects

    My Account

    LoginRegister

    Statistics

    View Usage Statistics

    DSpace software copyright © 2002-2015  DuraSpace
    Contact Us | Send Feedback
    Theme by 
    @mire NV