| dc.description.abstract | The relationship between multiloop design and Bristol gains of a multivariable plant is shown. The Bristol and relative gains are distinguished. The Bristol gains B characterize the plant and the relative gains Λ characterize the designed feedback system. It is Λ, not B, that determines the interaction in loop designs. Λ is equal to B in a loop only at frequencies where all other loop gains are much above 0dB, usually significantly below the respective loop gain crossover frequencies. Λ=1 in a loop at frequencies where all other loop gains are much below 0dB, usually significantly above the respective loop gain crossover frequencies. The transition of Λ in a loop from B to 1 in the important medium frequency range is one of the most interesting and under-researched aspects of loop design interaction. | |
| dc.publisher | The American Society of Mechanical Engineers (ASME) | |
| dc.title | On Multiloop Interaction and Relative and Bristol Gains | |
| dc.type | Journal Paper | |
| dc.journal.volume | 128 | |
| dc.journal.issue | 4 | |
| dc.journal.title | Journal of Dynamic Systems, Measurement, and Control | |
| dc.identifier.doi | 10.1115/1.2363412 | |
| dc.journal.fristpage | 929 | |
| dc.journal.lastpage | 937 | |
| dc.identifier.eissn | 1528-9028 | |
| dc.keywords | Design | |
| dc.keywords | Industrial plants | |