Show simple item record

dc.contributor.authorChi-Chuan Wang
dc.contributor.authorSenior Researcher
dc.contributor.authorMin-Sheng Liu
dc.contributor.authorAssociate Researcher
dc.contributor.authorJin-Sheng Leu
dc.contributor.authorResearcher
dc.date.accessioned2017-05-09T00:04:41Z
dc.date.available2017-05-09T00:04:41Z
dc.date.copyrightMarch, 2001
dc.date.issued2001
dc.identifier.issn0195-0738
dc.identifier.otherJERTD2-26494#100_1.pdf
dc.identifier.urihttp://yetl.yabesh.ir/yetl/handle/yetl/125105
dc.description.abstractThis study experimentally investigates the effect of circuitry on the refrigerant-side pressure drops of plate finned tube evaporators. Experiments were performed with countercross, parallel-cross, and z-shape arrangements. The results showed that the parallel-cross-flow circuit gives a lower pressure drop than other arrangements. Generally, the refrigerant-side pressure drops increase with air frontal velocities. However, for G=200 kg/m2⋅s and parallel flow, the pressure drops decrease with increase of air frontal velocity. This unusual characteristic is most likely related to the flow pattern transition when subjected to heat addition.
dc.publisherThe American Society of Mechanical Engineers (ASME)
dc.titleInfluence of Circuitry Arrangement on the Pressure Drops of Two-Row Finned Tube Evaporators
dc.typeJournal Paper
dc.journal.volume123
dc.journal.issue1
dc.journal.titleJournal of Energy Resources Technology
dc.identifier.doi10.1115/1.1348271
dc.journal.fristpage100
dc.journal.lastpage103
dc.identifier.eissn1528-8994
dc.keywordsFlow (Dynamics)
dc.keywordsPressure drop
dc.keywordsRefrigerants
dc.keywordsHeat AND Shapes
dc.treeJournal of Energy Resources Technology:;2001:;volume( 123 ):;issue: 001
dc.contenttypeFulltext


Files in this item

Thumbnail

This item appears in the following Collection(s)

Show simple item record