    Abstract
    The performance of a nominally 10.5-kW (3-ton) vapor-compression refrigeration system was numerically simulated for air flow rates across the condenser heat exchanger between 60 and 150 percent of the standard value. The results can be used for estimating the energy and cost savings achievable by restoring standard air flow rates across partially blocked condensers of vapor-compression refrigeration systems. The system coefficient of performance was predicted to decrease by 7.6 percent from its value of 2.912 at standard air flow when air flow across the condenser decreased by 40 percent. The associated pressure rise across the compressor increased by 19 percent above its standard value of 1151 kPa, suggesting that reduced compressor life might be the major economic consequence of condenser air flow blockage.
    URI
    http://yetl.yabesh.ir/yetl/handle/yetl/115196
    Collections
    • Journal of Energy Resources Technology

    DSpace software copyright © 2002-2015  DuraSpace
    Contact Us | Send Feedback
    Theme by 
    @mire NV
     

     

    Browse

    All of DSpaceCommunities & CollectionsBy Issue DateAuthorsTitlesSubjectsThis CollectionBy Issue DateAuthorsTitlesSubjects

    My Account

    LoginRegister

    Statistics

    View Usage Statistics

    DSpace software copyright © 2002-2015  DuraSpace
    Contact Us | Send Feedback
    Theme by 
    @mire NV