Show simple item record

dc.contributor.authorC. F. Kettleborough
dc.contributor.authorD. G. Waugaman
dc.contributor.authorM. Johnson
dc.date.accessioned2017-05-08T23:38:11Z
dc.date.available2017-05-08T23:38:11Z
dc.date.copyrightSeptember, 1992
dc.date.issued1992
dc.identifier.issn0195-0738
dc.identifier.otherJERTD2-26446#181_1.pdf
dc.identifier.urihttp://yetl.yabesh.ir/yetl/handle/yetl/110120
dc.description.abstractEvaporative coolers consist of two main types: (a) the direct evaporative cooler in which water mixes with the air to be cooled; and (b) the indirect evaporative cooler in which water is sprayed into alternate passages cooling the secondary airflow, which in turns cools the primary flow which then passes to the building to be cooled. A three-dimensional numerical evaluation of the indirect cooler is given. Energy and mass balance equations are derived for the primary and secondary flows and the effectiveness is calculated for different variable inlet velocities and compared with experimental values.
dc.publisherThe American Society of Mechanical Engineers (ASME)
dc.titleThe Thermal Performance of the Cross-Flow Three-Dimensional Flat Plate Indirect Evaporative Cooler
dc.typeJournal Paper
dc.journal.volume114
dc.journal.issue3
dc.journal.titleJournal of Energy Resources Technology
dc.identifier.doi10.1115/1.2905939
dc.journal.fristpage181
dc.journal.lastpage186
dc.identifier.eissn1528-8994
dc.keywordsEvaporative cooling
dc.keywordsFlat plates
dc.keywordsCross-flow
dc.keywordsWater
dc.keywordsFlow (Dynamics)
dc.keywordsCooling
dc.keywordsAir flow
dc.keywordsEquations AND Coolers
dc.treeJournal of Energy Resources Technology:;1992:;volume( 114 ):;issue: 003
dc.contenttypeFulltext