Show simple item record

dc.contributor.authorJ. M. O’Reilly
dc.contributor.authorP. F. Monaghan
dc.date.accessioned2017-05-08T23:38:11Z
dc.date.available2017-05-08T23:38:11Z
dc.date.copyrightDecember, 1992
dc.date.issued1992
dc.identifier.issn0195-0738
dc.identifier.otherJERTD2-26447#286_1.pdf
dc.identifier.urihttp://yetl.yabesh.ir/yetl/handle/yetl/110109
dc.description.abstractWind evaporators are alternative evaporators for air source heat pumps which rely on wind-driven or natural convection to move air across the heat transfer surfaces. A fully automatic, computer-controlled test facility which allows side-by-side testing of wind evaporator and conventional heat pumps and monitoring of weather conditions has been designed and built at University College Galway. The aim of this paper is to quantify the advantages of wind evaporators by comparing the performance of a wind evaporator heat pump with that of a conventional heat pump over an extended testing period and by examining the relationship between weather conditions and heat pump performance. In this paper, results are presented in the form of plots of coefficient of performance (COP), compressor power, evaporator and condenser heat transfers and climatic variables against time. In addition, a testing period coefficient of performance has been calculated for each heat pump. The results show that wind speed is the dominant climatic variable affecting wind evaporator heat pump performance, and that frost growth does not significantly reduce this performance. Even at extremely low wind speeds, the COP of the wind evaporator heat pump is not significantly affected. After over 460 hr of testing, the testing period COP of the wind evaporator heat pump shows a 16 percent increase over that of the conventional heat pump. (Refer to Nomenclature in Part I of this paper.)
dc.publisherThe American Society of Mechanical Engineers (ASME)
dc.titleWind Evaporator Heat Pumps—Part II: Thermal Performance Results
dc.typeJournal Paper
dc.journal.volume114
dc.journal.issue4
dc.journal.titleJournal of Energy Resources Technology
dc.identifier.doi10.1115/1.2905955
dc.journal.fristpage286
dc.journal.lastpage290
dc.identifier.eissn1528-8994
dc.keywordsHeat pumps
dc.keywordsWind
dc.keywordsTesting
dc.keywordsHeat transfer
dc.keywordsWind velocity
dc.keywordsNatural convection
dc.keywordsCompressors
dc.keywordsComputers
dc.keywordsCondensers (steam plant) AND Test facilities
dc.treeJournal of Energy Resources Technology:;1992:;volume( 114 ):;issue: 004
dc.contenttypeFulltext


Files in this item

Thumbnail

This item appears in the following Collection(s)

Show simple item record