description abstractAn experimental study on a pump-driven loop heat pipe (PLHP) charged with R22 for cooling a data center is reported in this paper. The PLHP had five tube-fin heat exchangers as evaporators and three tube-fin heat exchangers as condensers, a liquid reservoir, and a canned motor pump. The coefficient of performance of the unit was 3.75 when the indoor-outdoor temperature difference was 10°C, then increased to 9.37 when the temperature difference was 25°C. The mass flow rates of R22 increased from 200 to
publisherAmerican Society of Civil Engineers
titleExperimental Study on a Pump Driven Loop-Heat Pipe for Data Center Cooling
typeJournal Paper
journal volume141
journal issue4
journal titleJournal of Energy Engineering
identifier doi10.1061/(ASCE)EY.1943-7897.0000253
treeJournal of Energy Engineering:;2015:;Volume ( 141 ):;issue: 004
contenttypeFulltext