Show simple item record

contributor authorIk-Seong Joo
contributor authorMingsheng Liu
date accessioned2017-05-08T21:22:03Z
date available2017-05-08T21:22:03Z
date copyrightDecember 2003
date issued2003
identifier other%28asce%291076-0431%282003%299%3A4%28126%29.pdf
identifier urihttp://yetl.yabesh.ir/yetl/handle/yetl/48676
description abstractEconomizers modulate outside air intake to minimize/eliminate mechanical cooling in air-handling units when outside air enthalpy is lower than the return air enthalpy. A theoretical study is conducted to developed analytical economizer models, to investigate potential energy savings, and to develop a potential energy savings calculation method for dual-duct air-handling unit systems. The study found that economizers decrease cooling energy consumption without heating energy penalties for dual-fan, dual-duct air-handling units. Economizers have significant heating energy penalties for single-fan, dual-duct air-handling units.
publisherAmerican Society of Civil Engineers
titleEconomizer Application in Dual-Duct Air-Handling Units
typeJournal Paper
journal volume9
journal issue4
journal titleJournal of Architectural Engineering
identifier doi10.1061/(ASCE)1076-0431(2003)9:4(126)
treeJournal of Architectural Engineering:;2003:;Volume ( 009 ):;issue: 004
contenttypeFulltext


Files in this item

Thumbnail

This item appears in the following Collection(s)