description abstractThe possibility is investigated of using freon refrigerants and organic solvent systems in absorption refrigeration installations, utilizing low thermal-potential energy sources, for refrigeration and direct contact cooling to temperatures of or below 0°C. A detailed thermodynamic analysis by means of a simulation model of the cycle for several refrigerant-absorbent systems has delineated the operating range and dependence of the variations of the coefficient of performance and of the circulation ratio upon generator and condenser temperatures. The performance characteristics of freon - dibutyl phthalate and freon - dimethyl ether of tetraethylene glycol systems were compared.
publisherThe American Society of Mechanical Engineers (ASME)
titlePerformance Characteristics of Absorption Cooling Cycle Operated by Low Thermal Potential Energy Sources
typeJournal Paper
journal volume105
journal issue2
journal titleJournal of Manufacturing Science and Engineering
identifier doi10.1115/1.3185877
journal fristpage94
journal lastpage99
identifier eissn1528-8935
keywordsCooling
keywordsAbsorption
keywordsPotential energy
keywordsCycles
keywordsPerformance characterization
keywordsTemperature
keywordsRefrigerants
keywordsRefrigeration
keywordsCondensers (steam plant)
keywordsGenerators
keywordsPhthalate plasticizers
keywordsEthers (Class of compounds) AND Simulation models