| contributor author | M. W. Larinoff | |
| contributor author | L. L. Forster | |
| date accessioned | 2017-05-08T23:00:34Z | |
| date available | 2017-05-08T23:00:34Z | |
| date copyright | July, 1976 | |
| date issued | 1976 | |
| identifier issn | 1528-8919 | |
| identifier other | JETPEZ-26726#335_1.pdf | |
| identifier uri | http://yetl.yabesh.ir/yetl/handle/yetl/88563 | |
| description abstract | A new concept of power plant heat-sink system is presented which employs the combination of a conventional wet-tower and a conventional dry-tower. The purpose of this cooling system is to reduce wet cooling-tower makeup-water requirements in water-short areas. The dry tower operates all year around while the wet-peaking tower is used only above certain ambient dry-bulb temperatures. The two cooling circuits serve separate sections of a conventional, surface-type, steam condenser. Thermal performance analysis is presented for various combinations of cooling systems ranging from 100 percent wet to 100 percent dry. Annual makeup-water requirements are calculated for various sizes of towers located in 18 selected cities of the U.S.A. ranging from north to south and east to west. | |
| publisher | The American Society of Mechanical Engineers (ASME) | |
| title | Dry and Wet-Peaking Tower Cooling Systems For Power Plant Application | |
| type | Journal Paper | |
| journal volume | 98 | |
| journal issue | 3 | |
| journal title | Journal of Engineering for Gas Turbines and Power | |
| identifier doi | 10.1115/1.3446174 | |
| journal fristpage | 335 | |
| journal lastpage | 346 | |
| identifier eissn | 0742-4795 | |
| keywords | Cooling systems | |
| keywords | Power stations | |
| keywords | Water | |
| keywords | Temperature | |
| keywords | Cooling | |
| keywords | Circuits | |
| keywords | Condensers (steam plant) | |
| keywords | Cooling towers AND Heat sinks | |
| tree | Journal of Engineering for Gas Turbines and Power:;1976:;volume( 098 ):;issue: 003 | |
| contenttype | Fulltext | |