Show simple item record

contributor authorMichele Blazek
contributor authorHuimin Chong
contributor authorWoonsien Loh
contributor authorJonathan G. Koomey
date accessioned2017-05-08T21:21:22Z
date available2017-05-08T21:21:22Z
date copyrightSeptember 2004
date issued2004
identifier other%28asce%291076-0342%282004%2910%3A3%2898%29.pdf
identifier urihttp://yetl.yabesh.ir/yetl/handle/yetl/48208
description abstractAs information and communications technology matures, the nature of the infrastructure that supports it evolves and specializes. While the telephone infrastructure had been built as a network with central offices acting as hubs, the information and communications technology maintains a similar structure, but instead, has hubs of specialized Internet data centers which house the routers and servers. This paper updates one of the first studies to document the electricity consumption and power distribution within an Internet data center. For this study, electricity billing data, metering data, and facility floor space allocation data were used to calculate computer room, total computer room, and building power densities for July 2002. The results of this 2002 study indicate that although the data center had expanded its operations by roughly 33% from the previous year and increased the electricity demand associated with the computer equipment by 55%, the total computer room power density (which includes cooling and auxiliary equipment) remained the same as the previous year at 355 W/m
publisherAmerican Society of Civil Engineers
titleData Centers Revisited: Assessment of the Energy Impact of Retrofits and Technology Trends in a High-Density Computing Facility
typeJournal Paper
journal volume10
journal issue3
journal titleJournal of Infrastructure Systems
identifier doi10.1061/(ASCE)1076-0342(2004)10:3(98)
treeJournal of Infrastructure Systems:;2004:;Volume ( 010 ):;issue: 003
contenttypeFulltext