| description abstract | Abstract. Although radiative cooling research is widely found in the literature, no comprehensive study has yet been conducted on the impact of novel radiant cooling (>0.91 reflectance) on the energy efficiency of warehouses. In this work, we develop three building models based on a Department of Energy prototype warehouse model using trnsys, representing a typical warehouse with a black roof, a typical warehouse with a white roof, and a warehouse with novel radiative cooling (RC) paint on its roof. These models are run for 15 different cities, each representative of a different ASHRAE climate zone, to better understand the impact of RC in many different climates. It was found that an RC-coated roof in a warehouse could reduce the building's annual heating, ventilation, and air conditioning (HVAC) loads by up to 14.11 kWh/m2 of the roof area compared to a black roof, resulting in a maximum reduction in energy costs of 0.55 $/m2 or $2646/year for a large 4835 m2 warehouse. Similarly, replacing the typical white roof coating with an RC coating could reduce the warehouse's energy consumption by up to 8.17 kWh/ m2 of roof area, thus reducing energy costs by as much as 0.29 $/m2 or $1386/year for a 4835 m2 warehouse. In addition, applying RC paint to an unconditioned warehouse could reduce the building's ASHRAE Standard 55 indoor temperature exceedance by up to 1330 h/year compared to a black roof and up to 532 h/year compared to a white roof. | |