description abstractWind generally reduces the thermal effectiveness of air-cooled condensers (ACCs). Therefore, this study investigates wind screens as a means to improve the performance of a 20-fan induced draft ACC under windy conditions. Two wind-screen configurations are tested: walls extending above the fan platform (termed wind walls) and walls extending below the fan platform (termed wind skirts). The performance of this five-by-four ACC is evaluated using the open-source computational fluid dynamics code, OpenFOAM. The performance is first analyzed under windless operating conditions and then when the ACC is subjected to wind speeds of 3, 6, and 9 m/s directed along the shorter and longer axes of the ACC. Under windless conditions, wind walls increase the ACC’s thermal effectiveness by 1.0%. Wind skirts, however, reduce the effectiveness by 1.8%. Depending on the wind speed and direction, wind walls increase the mean thermal effectiveness of the ACC by 0.3–3.9% under windy conditions. Wind skirts, on the other hand, are only beneficial at higher wind speeds: At 3 m/s, the effectiveness declines by 1.4–2.1%; at 6 m/s, the change in effectiveness ranges from −0.4% to 2.2%; and at 9 m/s, the effectiveness increases by 2.4–3.8%. Wind walls are therefore considered more effective than wind skirts for the tested range of wind speeds.
publisherThe American Society of Mechanical Engineers (ASME)
titleThe Effect of Wind Screens on the Performance of an Induced Draft Air-Cooled Condenser Under Windless and Windy Conditions
typeJournal Paper
journal volume15
journal issue1
journal titleJournal of Thermal Science and Engineering Applications
identifier doi10.1115/1.4055331
journal fristpage11003-1
journal lastpage11003-9
page9
treeJournal of Thermal Science and Engineering Applications:;2022:;volume( 015 ):;issue: 001