Show simple item record

contributor authorShia, David
contributor authorYang, Jin
contributor authorSivapalan, Sean
contributor authorSoeung, Rithi
contributor authorAmoah-Kusi, Christian
date accessioned2022-02-06T05:43:58Z
date available2022-02-06T05:43:58Z
date copyright6/14/2021 12:00:00 AM
date issued2021
identifier issn1087-1357
identifier othermanu_143_11_111012.pdf
identifier urihttp://yetl.yabesh.ir/yetl1/handle/yetl/4278640
description abstractSingle-phase cold plate liquid cooling attracts more and more attention to high-performance computing (HPC), cloud computing, and general computing data centers for the thermal management of modern microprocessors and adjacent components due to liquid’s inherent advantage of higher specific heat compared to air. Deionized (DI) water is usually used as a coolant for liquid cooling in data centers. On the contrary, propylene glycol/water is recommended as a coolant for single-phase cold plate liquid cooling in this study for following reasons. The inhibited propylene glycol-based fluids of 25+% vol have the benefit of being biostatic and not requiring addition of biocides. They also offer freezing protection in the usage of data centers in cold climates. The cold plates made from copper is prone to oxide even under the room temperature, and the dissimilarity between brazing material and copper can also cause galvanic corrosion in the usage. In this paper, a study was carried out to investigate cold plate corrosion with inhibited propylene glycol/water using design of experiments (DOE) method. This study shows manufacturing process plays an important role on corrosion of cold plates made from copper and the corrosion risk can be mitigated by enabling new manufacturing processes, including friction stir welding (FSW) and nickel plating to the inside surface of the cold plate in the manufacturing process.
publisherThe American Society of Mechanical Engineers (ASME)
titleCorrosion Study on Single-Phase Liquid Cooling Cold Plates With Inhibited Propylene Glycol/Water Coolant for Data Centers
typeJournal Paper
journal volume143
journal issue11
journal titleJournal of Manufacturing Science and Engineering
identifier doi10.1115/1.4051059
journal fristpage0111012-1
journal lastpage0111012-7
page7
treeJournal of Manufacturing Science and Engineering:;2021:;volume( 143 ):;issue: 011
contenttypeFulltext