Show simple item record

contributor authorShah, Jimil M.
contributor authorMisrak, Abel
contributor authorAgonafer, Dereje
contributor authorKaler, Mike
date accessioned2019-09-18T09:08:09Z
date available2019-09-18T09:08:09Z
date copyright5/8/2019 12:00:00 AM
date issued2019
identifier issn1043-7398
identifier otherep_141_03_031003
identifier urihttp://yetl.yabesh.ir/yetl1/handle/yetl/4259269
description abstractContamination due to the use of airside economizer has become a major issue that cost companies revenue. This issue will continue to rise as server components become smaller, densely packed, and as companies move into more polluted environments. Contaminants with small particles less than 10 μm are not noticeable; yet, these particles are most likely to get to areas where they can cause damage. Dust from different sources and suspended in air settles on surfaces of electrical components. The dust mainly contains two components: salts and metallic particles. The salts may be neutral or corrosive and the nature of the salt depends on the deliquescent humidity. For metallic particles, surveys are performed in various data centers in order to determine the limits in terms of weight per unit area and particle size distribution. It is necessary to first identify those contaminants that directly affect the information technology (IT) equipment in the data center. In this research, a real-world data center utilizing airside economization in an ANSI/ISA classified G2 environment was chosen for the study. Servers were removed and qualitative study of cumulative corrosion damage was carried out. The particulate contaminants were collected from different locations of a server and material characterization was performed using scanning electron microscopy (SEM), energy dispersive spectrometer (EDS), and Fourier transform infrared spectroscopy (FTIR). The analysis from these results helps to explain the impact of the contaminants on IT equipment reliability.
publisherAmerican Society of Mechanical Engineers (ASME)
titleIdentification and Characterization of Particulate Contaminants Found at a Data Center Using Airside Economization
typeJournal Paper
journal volume141
journal issue3
journal titleJournal of Electronic Packaging
identifier doi10.1115/1.4043481
journal fristpage31003
journal lastpage031003-10
treeJournal of Electronic Packaging:;2019:;volume( 141 ):;issue: 003
contenttypeFulltext


Files in this item

Thumbnail

This item appears in the following Collection(s)

Show simple item record