description abstractIn general, smaller fans operate at lower efficiencies than larger fans of proportional linear dimensions. In this work, the applicability of replacing smaller, 60 mm baseline fans from within the chassis of web servers with an array of larger, geometrically proportional 80 mm and 120 mm fans consolidated to the back of a rack is experimentally tested. Initial characterization of the selected fans showed that the larger fans operate at double peak total efficiency of the smaller fans. A stack of four servers were used in a laboratory setting to represent a rack of servers. When all four servers were stressed at uniform computational loadings, the 80 mm fans resulted in 50.1–52.6% reduction in total rack fan power compared to the baseline fans. The 120 mm fans showed similar reduction in rack fan power of 47.6–54.0% over the baseline. Since actual data centers rarely operate at uniform computational loading across servers in a rack, a worst case scenario test was conceived in which the array of larger fans were controlled by a single server operating at peak computational workload while the other three in the rack remained idle. Despite significant overcooling in the three idle servers, the 80 mm and 120 mm fan configurations still showed 35% and 34% reduction in total rack fan power compared to the baseline fans. The findings strongly suggest that a rack-level fan scheme in which servers share airflow from an array of consolidated larger fans is superior to traditional chassis fans.
publisherThe American Society of Mechanical Engineers (ASME)
titleEffectiveness of Rack-Level Fans—Part I: Energy Savings Through Consolidation
typeJournal Paper
journal volume139
journal issue4
journal titleJournal of Electronic Packaging
identifier doi10.1115/1.4038235
journal fristpage41011
journal lastpage041011-7
treeJournal of Electronic Packaging:;2017:;volume( 139 ):;issue: 004
contenttypeFulltext


Files in this item

Thumbnail

This item appears in the following Collection(s)

Show simple item record