Show simple item record

contributor authorFernandes
contributor authorJohn Edward;Eiland
contributor authorRichard;Nagendran
contributor authorBharath;Mulay
contributor authorVeerendra;Agonafer
contributor authorDereje
date accessioned2017-12-30T11:44:08Z
date available2017-12-30T11:44:08Z
date copyright10/27/2017 12:00:00 AM
date issued2017
identifier issn1043-7398
identifier otherep_139_04_041012.pdf
identifier urihttp://138.201.223.254:8080/yetl1/handle/yetl/4242991
description abstractFan efficiency is known to increase with size. In part I of this study, savings in server fan power on the order of 50% were reported by replacing server-enclosed 60 mm fans with a rear-mounted wall of larger fans (80 mm or 120 mm in size). A methodology for row-wise control of such rack-level fans, with the purpose of simulating an actual product, is previewed and savings comparable to part I are reported. Performance under real-life scenarios such as nonuniform computational loads and fan failure is investigated. Each rack-level setup has distinct advantages. Selecting between configurations would necessitate a compromise between efficiency, redundancy, and cost.
publisherThe American Society of Mechanical Engineers (ASME)
titleEffectiveness of Rack-Level Fans—Part II: Control Strategies and System Redundancy
typeJournal Paper
journal volume139
journal issue4
journal titleJournal of Electronic Packaging
identifier doi10.1115/1.4038014
journal fristpage41012
journal lastpage041012-9
treeJournal of Electronic Packaging:;2017:;volume( 139 ):;issue: 004
contenttypeFulltext


Files in this item

Thumbnail

This item appears in the following Collection(s)

Show simple item record