Show simple item record

contributor authorGurudath Nayak, H.
contributor authorVenkatarathnam, G.
date accessioned2017-11-25T07:19:27Z
date available2017-11-25T07:19:27Z
date copyright2017/11/4
date issued2017
identifier issn1948-5085
identifier othertsea_009_03_031012.pdf
identifier urihttp://138.201.223.254:8080/yetl1/handle/yetl/4235827
description abstractAuto refrigerant cascade (ARC) refrigerators are used extensively in the semiconductor manufacturing industry to provide refrigeration in the temperature range of 80–150 K. The performance of the ARC refrigerator depends on the mixture composition, operating pressures, etc. ARC refrigerators employ one or more liquid–vapor phase separators to separate the compressor lubricating oil and the condensed high boiling components and return to the compressor at an intermediate temperature to prevent freezing of the compressor lubricating oil and high boilers at low temperatures. However, dry-out of the phase separator can occur at some conditions. The phase separator dry-out phenomenon in ARC refrigerators has been studied experimentally with different mixtures and operating temperatures, the results of which are reported in this paper. The results of the studies show that the temperature difference between the streams at the cold end of the first heat exchanger can be used to reliably predict the dry-out of the phase separator.
publisherThe American Society of Mechanical Engineers (ASME)
titleOccurrence of Dry-Out Phenomenon in an Auto Refrigerant Cascade Refrigerator Operating With Zeotropic Mixtures
typeJournal Paper
journal volume9
journal issue3
journal titleJournal of Thermal Science and Engineering Applications
identifier doi10.1115/1.4035940
journal fristpage31012
journal lastpage031012-6
treeJournal of Thermal Science and Engineering Applications:;2017:;volume( 009 ):;issue: 003
contenttypeFulltext


Files in this item

Thumbnail

This item appears in the following Collection(s)

Show simple item record