Show simple item record

contributor authorC. L. Hosler
contributor authorJ. Pena
contributor authorR. Pena
date accessioned2017-05-09T01:38:07Z
date available2017-05-09T01:38:07Z
date copyrightJuly, 1974
date issued1974
identifier issn1528-8919
identifier otherJETPEZ-26711#283_1.pdf
identifier urihttp://yetl.yabesh.ir/yetl/handle/yetl/164753
description abstractThe purpose of this paper is to provide a method for estimating the deposition rate of the salt ejected in drift drops from a cooling tower in which salt water is circulated. The surface over which the salt will be distributed depends upon the wind speed, the maximum height the drops can reach, and the drop fall velocities. The drop fall velocity changes because of the evaporation in the air outside of the plume. The rate and extent of the evaporation is a function of the drop size, salt concentration, and ambient relative humidity. Three degrees of evaporation have been considered: (1) no evaporation; (2) evaporation to saturated solution and (3) evaporation to dry salt particles. For each degree of evaporation a graph was constructed that permits determination of the distance from the tower at which the salt contained in given drop size will fall. To use these graphs, the salt concentration, wind speed, and the maximum height a drop can reach must be known. The choice of the graph to be used for a particular case is made on the basis of humidity data for the site and the drift drop size. Corrections to compensate for the errors introduced by some of the assumptions are presented.
publisherThe American Society of Mechanical Engineers (ASME)
titleDetermination of Salt Deposition Rates From Drift From Evaporative Cooling Towers
typeJournal Paper
journal volume96
journal issue3
journal titleJournal of Engineering for Gas Turbines and Power
identifier doi10.1115/1.3445807
journal fristpage283
journal lastpage291
identifier eissn0742-4795
keywordsParticulate matter
keywordsWind velocity
keywordsEvaporative cooling
keywordsDrops
keywordsPlumes (Fluid dynamics)
keywordsEvaporation
keywordsCooling towers
keywordsErrors AND Water
treeJournal of Engineering for Gas Turbines and Power:;1974:;volume( 096 ):;issue: 003
contenttypeFulltext