| description abstract | This study presents an experimental investigation of the characteristics of convective heat transfer in horizontal shell and coil heat exchangers in addition to the friction factor for fully developed flow through their helically coiled tube (HCT). Five heat exchangers of counterflow configuration were constructed with different HCTcurvature ratios (خ´) and tested at different mass flow rates and inlet temperatures of خ³Al2O3/water nanofluid in the HCT. The tests were performed for خ³Al2O3 with average size of 40 nm and particles volume concentration (د•) from 0% to 2% for 0.0392≤خ´â‰¤0.1194. Totally, 750 test runs were performed from which the HCTaverage Nusselt number (Nuآ¯t) and fanning friction factor (fc) were calculated. Results illustrated that Nuآ¯t and fc of nanofluids are higher than those of the pure water at same flow condition, and this increase goes up with the increase in د•. When د• increases from 0% to 2%, the average increase in Nuآ¯t is of 59.4–81% at lower and higher HCTReynolds number, respectively, and the average increase in fc is of 25.7% and 27.4% at lower and higher HCTReynolds number, respectively, when د• increases from 0% to 2% for خ´=0.1194. In addition, results showed that Nuآ¯t and fc increase by increasing coil curvature ratio. When خ´ increases from 0.0392 to 0.1194 for د•=2%, the average increase in Nuآ¯t is of 130.2% and 87.2% at lower and higher HCTReynolds number, respectively, and a significant increase of 18.2–7.5% is obtained in the HCTfanning friction factor at lower and higher HCTReynolds number, respectively. Correlations for Nuآ¯t and fc as a function of the investigated parameters are obtained. | |