description abstractThis paper deals with the distribution of airflow and the resulting cooling in a data center. First, the cooling challenge is described and the concept of a raised-floor data center is introduced. In this arrangement, cooling air is supplied through perforated tiles. The flow rates of the cooling air must meet the cooling requirements of the computer servers placed next to the tiles. These airflow rates are governed primarily by the pressure distribution under the raised floor. Thus, the key to modifying the flow rates is to influence the flow field in the under-floor plenum. Computational fluid dynamics (CFD) is used to provide insight into various factors affecting the airflow distribution and the corresponding cooling. A number of ways of controlling the airflow distribution are explored. Then attention is turned to the above-floor space, where the focus is on preventing the hot air from entering the inlets of computer serves. Different strategies for doing this are considered. The paper includes a number of comparisons of measurements with the results of CFD simulations.
publisherThe American Society of Mechanical Engineers (ASME)
titleAirflow and Cooling in a Data Center
typeJournal Paper
journal volume132
journal issue7
journal titleJournal of Heat Transfer
identifier doi10.1115/1.4000703
journal fristpage73001
identifier eissn1528-8943
keywordsFlow (Dynamics)
keywordsCooling
keywordsAir flow
keywordsData centers
keywordsTiles
keywordsServer racks
keywordsInterior walls AND Pressure
treeJournal of Heat Transfer:;2010:;volume( 132 ):;issue: 007
contenttypeFulltext


Files in this item

Thumbnail

This item appears in the following Collection(s)

Show simple item record