Show simple item record

contributor authorD. H. Bultman
contributor authorL. C. Burmeister
contributor authorV. Bortone
date accessioned2017-05-08T23:46:58Z
date available2017-05-08T23:46:58Z
date copyrightDecember, 1995
date issued1995
identifier issn0195-0738
identifier otherJERTD2-26462#349_1.pdf
identifier urihttp://yetl.yabesh.ir/yetl/handle/yetl/115196
description abstractThe performance of a nominally 10.5-kW (3-ton) vapor-compression refrigeration system was numerically simulated for air flow rates across the condenser heat exchanger between 60 and 150 percent of the standard value. The results can be used for estimating the energy and cost savings achievable by restoring standard air flow rates across partially blocked condensers of vapor-compression refrigeration systems. The system coefficient of performance was predicted to decrease by 7.6 percent from its value of 2.912 at standard air flow when air flow across the condenser decreased by 40 percent. The associated pressure rise across the compressor increased by 19 percent above its standard value of 1151 kPa, suggesting that reduced compressor life might be the major economic consequence of condenser air flow blockage.
publisherThe American Society of Mechanical Engineers (ASME)
titleEffects of Condenser Air Flow Blockage on Vapor-Compression Refrigerator Performance
typeJournal Paper
journal volume117
journal issue4
journal titleJournal of Energy Resources Technology
identifier doi10.1115/1.2835434
journal fristpage349
journal lastpage353
identifier eissn1528-8994
keywordsVapors
keywordsAir flow
keywordsCompression AND Condensers (steam plant)
treeJournal of Energy Resources Technology:;1995:;volume( 117 ):;issue: 004
contenttypeFulltext